Remote control float valve may have the following three common faults One: Pool overflow A. Damaged pilot valve rubber gasket B. Leakage of float ball joint C. Connecting rod piston The object is stuck A. Replace the spacer B. Replace the float C. Remove foreign objects II: The water level is too low A. There is debris in the pilot valve body B. The connecting rod piston gets caught by the foreign matter A. Remove the impurities B. Adjust it Three: There is an abnormal sound A. There is debris in the main valve body B. The speed of closing is unreasonable A. Remove impurities B. Adjust needle valve opening degree Remote float valve maintenance and troubleshooting Removal of the main valve of the remote float valve (1) Remove the external piping and control valve; (2) symmetrically loosen the nut by diagonal money, screw into the top wire, remove the valve cover, and remove the spring; (3) Unscrew the valve stem retraction nut and remove the diaphragm pressure plate and diaphragm; (4) Remove the valve flap, pad pressure plate and large O-type apron; counterclockwise release the valve seat and remove the asbestos gasket. Through the above troubleshooting method can basically solve the problem of floating ball valve remote control failure, if you can not solve the problem, you can contact the valve manufacturer after-sales service. Carton Glue,Hot Melt Adhesive Granules,Hot Melt Adhesive,Carton Adhesive Hetrun Industry Group Limited , https://www.hetrunindustry.com