Transformer Empty Load Tester Features

Transformer Empty Load Tester Features:
1. It can measure the no-load current, no-load loss, short-circuit voltage, short-circuit loss and zero-sequence impedance of various types of transformers.
2. Transformer empty load characteristic tester can automatically perform waveform distortion correction, temperature correction, voltage correction (no-load test under non-rated voltage), current correction (short-circuit test under non-rated current conditions), and additional loss correction of short-circuit test, The operator can automatically calculate the corrected result by simply inputting the correction index instrument according to the transformer type.
3, allow external voltage transformer and current transformer for extended range measurement.
4, transformer load tester voltage and current measurement circuit wide limit: the maximum voltage can be measured to 750V, without switching gear to ensure accuracy. The instrument itself will not be damaged due to the wrong selection of the voltage range; the current can pass 100A current test.